松下UPS蓄电池LC-P系列(17AH--200Ah)槽、盖阻燃性等级达到UL-V0级
松下UPS蓄电池LC-P系列槽、盖应采用高强度ABS材料制造,并具有阻燃性,阻燃性等级达到UL-V0级,正常工作条件下不出现鼓胀或收缩变形。 松下蓄电池应通过UL、CE产品安全认证,并提供相关复印件和查询地址。
松下蓄电池设置放电旁路开关,用于蓄电池核对性及充放电但不影响馈电母线供电。(放电旁路开关视情况安装在直流柜或蓄电池室)。
松下电池的极柱应由合金或铜芯铅制成(或更优),防止裂隙,在维持最低电压降的同时,能承受强大的电流以保证大放电时(1h放电率)极板应牢固地焊接到接线柱上,接线柱和连接部件应耐酸﹑耐腐蚀。
松下蓄电池电压均衡性应满足一组蓄电池中任意二个电池的开路电压差不超过20mV(2V蓄电池)。
沈阳松下蓄电池连接板应保证稳固连接电池间的端子,不可使用若干较短的连接板及螺丝进行连接使其加长。各连接点考虑防腐。蓄电池间的连接条电压降3I10时不超过8mV。
Panasonic UPS BATTERY LC-P series (17AH- 200Ah) groove, cover flame retardant rating to UL-V0 level
Panasonic UPS battery LC-P series slot, cover should be made of high strength ABS material, and has flame retardant, flame retardant grade reaches UL-V0 level, under normal working conditions, there is no bulge or contraction deformation. Panasonic battery should pass UL, CE product safety certification, and provide relevant copies and query address.
Panasonic battery discharge bypass switch, used for battery verification and charge and discharge, but does not affect the feeder bus power supply. (Discharge bypass switch is installed in dc cabinet or battery room according to the situation).
Panasonic battery pole should be made of alloy or copper core lead (or better), to prevent cracks, in the maintenance of the lowest voltage at the same time, can withstand strong current to ensure a large discharge (1h discharge rate) plate should be firmly welded to the terminal, the terminal and connecting parts should be acid resistant, corrosion resistant.
Matsushita battery voltage balance should meet any two batteries in a group of batteries open circuit voltage difference does not exceed 20mV (2V battery).
Shenyang Matsushita battery connecting plate should ensure that the terminal between the battery is firmly connected, can not use a number of shorter connecting plate and screws to connect the extension. Consider corrosion protection at each connection point. When the voltage of the connection bar between the batteries is 3I10, the voltage does not exceed 8mV.